|

CROSS-CONNECTION CONTROL/BACKFLOW
PREVENTION
INTRODUCTION
The Department of
Environmental Protection (DEP) is authorized under the Pennsylvania Safe
Drinking Water Act to establish standards for the construction of a water supply
to assure compliance with the provisions of the act. Accordingly, Section
109.608 of DEP’s rules and regulations, requires that "a public water
system may not be designed or constructed in a manner which creates a
cross-connection." In addition, Section 109.709(b) further requires
that "At the direction of DEP, the public water supplier shall develop and
implement a comprehensive control program for the elimination of existing
cross-connections or the effective containment of sources of contaminations, and
prevention of future cross-connections."
DEFINITIONS
1. Air Gap Separation
- The unobstructed vertical distance through the free atmosphere between the
lowest opening from any pipe or faucet supplying potable water to a tank,
plumbing fixture, or other device and the flood level rim of the receptacle.
The differential distance shall be at least double the diameter (2 x D) of
the supply pipe measured vertically above the top of the rim of the vessel.
In no case, shall the air gap be less than one inch.
2. Approved - A
backflow prevention device or method that has been accepted by the public
water supplier as suitable for the proposed use.
3. Atmospheric Vacuum
Breaker (AVB) - A fixture outlet device containing an optional shutoff
valve followed by a valve body containing a soft-seated float-check, a check
seat and an air inlet port. If the shutoff valve is open, the flow of water
causes the float to close the air inlet port. If the shutoff valve is
closed, the float falls and forms a check valve against backsiphonage and at
the same time opens the air inlet port. If no shutoff valve is provided, the
flow of water will determine the opening and closing of the air inlet port.
4. Auxiliary Water System
- Any water source or system on the premises of, or available to, the
customer except connections to other approved community water supply
systems.
5. Backflow - A flow
condition, induced by a differential in pressure, that causes the flow of
water or mixtures of water and other substances into the distribution pipes
of a potable water supply system from a source other than its intended
source. Backflow can result from either backsiphonage or backpressure.
6. Backflow Preventer
- A device or other means which will prevent the backflow of water or any
other substance into the public water supply system.
7. Backpressure - The
backflow of water or a mixture of water and other substances from a plumbing
fixture or other customer source, into a public water supply system due to
an increase of pressure in the fixture or customer source to a value that
exceeds the system pressure.
8. Backsiphonage - The
backflow of water or a mixture of water and other substances from a plumbing
fixture or other customer source, into a public water supply system due to a
temporary negative or sub-atmospheric pressure within the public water
supply system.
9. Consumer - The
owner or person in control of any premises supplied by or in any manner
connected to a public water supply system.
10. Consumer’s Water
System - Any water system, located on the consumer’s premises,
supplied by or in any manner connected to a public water supply system. A
household plumbing system is considered to be a consumer’s water system.
11. Containment -
Cross-connection control which isolates the customer’s entire facility
from the public water supply system so as to provide the protection
necessary to prevent contamination of the public water supply in the event
of backflow from the customer’s facility. Though containment control
prevents contamination of the public water supply, it offers no protection
to the water distribution system within the facility. Reduced pressure zone
devices are used for containment control.
12. Contamination -
The degradation of the quality of the drinking water by wastewaters,
processed fluids, or any water of a quality less than accepted drinking
water quality to a degree which would create an actual hazard to the public
health through poisoning or through the spread of disease.
13. Cross-connection -
An arrangement allowing either a direct or indirect connection through which
backflow, including backsiphonage, can occur between the drinking water in a
public water system and a system containing a source or potential source of
contamination, or allowing treated water to be removed from any public water
system, used for any purpose or routed through any device or pipes outside
the public water system, and returned to the public water system. The term
does not include connections to devices totally within the control of one or
more public water systems and connections between water mains.
14. Degree of Hazard -
An evaluation of the potential risk to health and the adverse effect upon
the public water supply system.
15. Double Check Valve
Assembly (DCVA) - An assembly composed of two single, independently
acting, soft-seated, spring-loaded check valves including tightly closing
shutoff valves located at each end of the assembly and suitable connections
for testing the water tightness of each check valve.
16. Fixture Outlet
Protection - Cross-connection control which isolates all free-flowing
fixture outlets (i.e., faucets) from the water distribution system within a
facility. Fixture outlet protection prevents backflow contamination of both
the facility water system and the public water supply. Examples of fixture
outlet protection devices include atmospheric vacuum breakers, hose-bibb
vacuum breakers, and pressure vacuum breakers.
17. Health Hazard -
Any condition, device, or practice in a water system or its operation that
creates, or may create, a danger to the health and well being of its users.
The word "severe", as used to qualify "health hazard",
means a hazard to the health of the user that could reasonably be expected
to result in significant morbidity or death.
18. Hose-Bibb Vacuum
Breaker (HBVB) - A fixture outlet device that contains a soft-seated,
spring-loaded, air inlet valve and is designed to be attached to an outlet
having a hose connection thread.
19. Interchangeable
Connection - An arrangement or device that will allow alternate, but not
simultaneous, use of two sources of water.
20. Internal Protection
- Cross-connection control which isolates all non-outlet, water-use
appliances within a facility (e.g., kitchen appliances, air conditioners,
boilers, process tanks, photo developing equipment) from the water
distribution system within the facility. Internal protection prevents
backflow contamination of both the facility water system and the public
water supply. Reduced pressure zone devices and double check valve
assemblies are used for internal protection.
21. Non-Health Hazard
- Any condition, device or practice in a water system or its operation that
creates, or may create, an impairment of the quality of the water to a
degree which does not create a hazard to the public health, but which does
adversely and unreasonably affect the aesthetic qualities of such water for
domestic use.
22. Non-Potable Water
- Water not safe for drinking, personal, culinary, or any other type of
domestic use.
23. Person - Any
individual, partnership, association, company, corporation, municipality,
municipal authority, political subdivision or any agency of federal or state
government. The term includes the officers, employees and agents of any
partnership, association, company, corporation, municipality, municipal
authority, political subdivision or any agency of federal or state
government.
24. Pollution - The
presence in water of any foreign substance that tends to degrade its quality
so as to constitute a hazard, or to impair the usefulness or quality of the
water to a degree which does not create an actual hazard to the public
health, but which does adversely and unreasonably affect such waters for
domestic use.
25. Potable Water -
Water which is satisfactory for drinking, personal, culinary, and domestic
purposes and meets the requirements of DEP.
26. Pressure Vacuum
Breaker (PVB) - A fixture outlet device containing an independently
operating, soft-seated, spring-loaded check valve and an independently
operating, soft-seated, spring-loaded, air inlet valve on the discharge side
of the check valve.
27. Process Fluids -
Any fluid or solution which may be chemically, biologically or otherwise
contaminated or polluted in a form or concentration such as would constitute
a health, pollutional, or system hazard if introduced into the public or a
consumer’s water system. This includes, but is not limited to:
a. Polluted or contaminated waters;
b. Process waters; sanitary quality;
d. Cooling waters;
e. Contaminated natural waters taken from
wells, lakes, streams, or irrigation systems;
f. Chemicals in solution or suspension;
g. Oils, gases, acids, alkalis, and other
liquid or gaseous fluids used in industrial or other processes, or for
fire fighting purposes;
h. Heating system waters from boilers or
heat pumps.
28. Public Water Supplier
- A person who owns or operates a public water system.
29. Public Water Supply
System - A system which provides water to the public for human
consumption which has at least 15 service connections or regularly serves an
average of at least 25 individuals daily at least 60 days out of the year.
The term includes any collection, treatment, storage, and distribution
facilities under control of the operator of the system and used in
connection with the system. The term includes collection or pretreatment
storage facilities not under such control which are used in connection with
the system. The term also includes a system which provides water for human
consumption via bottling, vending machines, retail sale, or bulk hauling
methods.
30. Reduced Pressure Zone
Device (RPZD) - A device which contains two independently acting,
soft-seated, spring-loaded check valves, together with a soft-seated,
spring-loaded, diaphragm-activated, pressure differential relief valve
located between the two check valves. During normal flow and at the
cessation of normal flow, the pressure between these two checks shall be
less than the supply pressure. In case of leakage of either check valve, the
differential relief valve, shall maintain the pressure between the checks at
less than the supply pressure by opening to the atmosphere. The device must
include tightly closing shutoff valves located at each end, and each device
shall be fitted with properly located test cocks.
31. Residential Dual Check
Valve (RDCV) - A non-testable backflow prevention device that is used
for containment control of residential homes and consists of two
independently operating, soft-seated, spring-loaded, consecutive check
valves.
32. Service Connection -
The terminal-end of a service line from the public water supply system. If a
meter is installed at the end of the service line, then the service
connection means the downstream end of the meter.
33. System Hazard - A
condition posing an actual or potential threat of damage to the physical
properties of the public water system or to the consumer’s potable water
system.
CROSS-CONNECTION CONTROL PROGRAM
Degree of Hazard
A. Hazardous Facilities
The following partial listing
gives examples of the types of facilities which would require an
acceptable reduced pressure zone device (RPZD) or air gap to be
installed in the service connection to the public water distribution system.
Additional facilities needing RPZDs or air gaps can be found in
Table 1.
|
Type of Facility
|
Potential Hazard
|
| Sewage,
industrial wastewater treatment plants and pumping stations, sewer
flushers, etc. |
Sewage,
industrial wastewater, contaminated water, toxic chemicals, etc. |
| Paper
manufacturing or processing, dye plants, petroleum processing and
storage facilities, printing plants, chemical manufacturing or
processing, industrial fluid systems, steam generation, rubber
processing, tanneries, etc. |
Toxic chemicals, water
conditioning compounds
Examples: Toxic dyes, acids,
alkalies, solvents, quaternary ammonia compounds, mercury, chromium |
| Canneries,
breweries, food processing, detergents, milk processing, ice
manufacturing, meat packers, poultry processing, rendering companies,
etc. |
Process
wastewater, steam, acids, caustics, refrigeration lines |
| Hospitals,
clinics, laboratories, solutions, veterinary hospitals, mortuaries,
embalmers, shipyards, marinas, nuclear reactor facilities |
Bacteria
cultures, laboratory blood and tissue waste, toxic materials, sea
water, sewage, contaminated water, etc. |
| Metal-plating,
photo processing, cleaning laundries, commercial car washes,
commercial refrigeration systems, dry cleaning establishments |
Toxic
chemicals, concentrated agents, solvents
Examples: Cyanides, fluorides,
copper, chromium, caustic and acid solutions, etc. |
| Commercial
greenhouses, spraying and irrigation systems using weedicides,
herbicides, exterminators |
Toxic chemicals
Examples: ammonium salts,
phosphates, 2,4-D, sodium arsenite, lindane, malathion, etc. |
| Boiler systems,
cooling towers or internal fire-fighting systems using conditioners,
inhibitors, etc. |
Toxic chemicals
Examples: Hydrazine, anti-freeze
solutions, etc. |
B.
Aesthetically Objectionable Facilities
The following partial listing
gives examples of the types of facilities which would require an
acceptable double check valve assembly (DCVA) device to be installed
in the service connection to the public water distribution system. Additional
facilities needing DCVAs can be found in Table 1.
|
Type of Facility
|
Potential Hazard
|
| Customer fire protection loops, fire
storage tanks with no chemical additives, fire systems with external pumping connections supplied by an
auxiliary source |
Stagnant
water, objectionable tastes, odors |
| High temperature potable water |
Objectionable
temperatures |
| Utilization of food grade dyes |
Objectionable
color |
| Complex plumbing systems in commercial buildings
Examples: Barber shops, beauty
salons, supermarkets |
Plumbing errors,
obsolete plumbing equipment, poor plumbing inspection/correction programs |
RECOMMENDED CROSS-CONNECTION
CONTROL
AND BACKFLOW PREVENTION DEVICES
3.0 General
In selecting for use of the
devices outlined in this section, it is vital that the degree of protection
provided be commensurate with the degree of hazard present. It also is
important that the limitations of each device be understood since the degree
of protection provided will depend on the type of backflow prevention device
and the maintenance program employed.
Acceptable backflow
prevention devices used for cross-connection control are as follows:
A. Air Gap
B. Double Check Valve Assembly (DCVA)*
C. Reduced Pressure Zone Devices (RPZD)*
D. Residential Dual Check Valve (RDCV)
E. Atmospheric Vacuum Breaker (AVB)
F. Hose-Bibb Vacuum Breaker (HBVB)
G. Pressure Vacuum Breaker (PVB)
*DCVAs and RPZDs should
conform to ANSI/AWWA Standards C510 and C511, respectively.
1. Air Gap
An air gap separation
provides a complete physical separation between the free flowing discharge
end of a potable water supply line, faucet, plumbing fixture, or other
device and the flood level rim of an open or nonpressure receiving vessel.
An acceptable air-gap separation shall be at least double the diameter of
the supply line. In no case shall the air gap be less than one inch. See
Figure 1.
Advantages:
By preventing backflow caused
by both backsiphonage and backpressure, air gap installations provide the
maximum degree of protection against backflow. Air gaps are recommended for
health hazard risks.
Limitations:
Air gap separations can be
defeated by the thoughtless addition of a hose that in effect extends the
discharge end of the pipe to a point below the highest possible water level
of the fixture. Fixture outlet devices should be installed when there is any
possibility of hose installation.
Under some conditions the
cost of an air gap separation may be high when compared to a mechanical
backflow prevention device.
Air gaps cause a loss of line
pressure. Therefore, certain commercial processes will need to re-establish
pressure through pumps or elevation.
Figure 1. Air Gap

|
Minimum Air Gaps for Plumbing Fixtures
Fixture
|
|
Fixture |
When Not Affected By Near
Wall (*)
(Inches)
|
When Affected By
Near Wall (**)
(Inches)
|
|
Laboratories and other fixtures with
effective opening not greater than 1/2 inch diameter |
1 |
1-1/2 |
|
Sink, laundry trays, goose-neck bath
faucets and other fixtures with effective openings not greater than
3/4inch diameter |
1-1/2 |
2-1/4 |
|
Over rim bath fillers and other fixtures
with effective openings not greater than one inch diameter |
2 |
3 |
|
Effective openings greater than one inches |
2X Diameter of Effective
Opening |
3X Diameter of Effective
Opening |
* Side walls, ribs or similar
obstructions do not effect air gaps when spaced from inside edge of spout
opening a distance greater than three times the diameter of the effective
opening for a single wall, or a distance greater than four times the diameter
of the effective opening for two intersecting walls.
** Vertical walls, ribs, or
similar obstructions extending from the water surface to or above the
horizontal plane of the spout opening require a greater air gap when spaced
closer to the nearest inside edge of spout opening than specified in (*)
above. The effect of three or more such vertical walls or ribs has not been
determined. In such cases, the air gap shall be measured from the top of the
wall.
2. Double Check Valve Assembly (DCVA)
The DCVA consists of two
independently acting, soft-seated, spring-loaded, check valves mounted in
series with two tightly closing shutoff valves and four test cocks (see
Figure 2.).
Advantages:
The primary advantage of a
DCVA is that when its two check valves are in the wide open position, there
is relatively little resistance to flow. The head loss through the device
ranges between 3 and 11 psi, depending on the rate of flow and diameter of
pipe.
Double check valve assemblies
prevent backflow caused by both backsiphonage and backpressure.
Limitations:
Because DCVAs lack the
differential pressure relief valve that RPZDs have, they are recommended
only for non-health hazard risks.
DCVAs have the inherent
weakness of possible failure without giving exterior indication that a
failure has occurred.
DCVAs are mechanical devices
that require periodic inspection and maintenance.
Figure 2. Double Check Valve
Assembly
Note: Check valves are in the
backflow position
3. Reduced Pressure Zone Device (RPZD)
This device consists of two
soft-seated, spring-loaded check valves operating in series, and a
soft-seated, spring-loaded, diaphragm-activated, pressure differential
relief valve, located in the zone between the check valves (see Figure 3.).
Two tightly closing shutoff valves and four test cocks complete the
assembly. These devices will indicate leakage through one or both check
valves or the relief valve by the discharge of water from the relief valve
port. This factor is an important advantage over the double check valve
assembly.
Advantages:
The RPZD, when periodically
tested and properly maintained, may be used for backflow protection in
situations where it would be extremely difficult, or impractical, to provide
an air gap separation.
Malfunctioning of the RPZD is
indicated by discharge of water from the relief port. The RPZD provides
protection from backflow caused by both backsiphonage and backpressure, and
is recommended for health hazard risks.
Limitations:
RPZDs are mechanical devices
that require periodic testing and maintenance.
Pressure loss through RPZDs
may be expected to average between 10 and 30 psi, depending upon the size
and flow rate of the device.
RPZDs should not be installed
below ground level, must be protected from freezing, and must be provided
with adequate space to facilitate maintenance and testing.
Figure 3. Reduced Pressure
Zone Device

Note: Check valves are in the
backflow position. The relief valve is in the normal flow position
4. Residential Dual Check Valve (RDCV) and the
Vacuum Breakers
Only the air gap, DCVA and
RPZD are testable devices that prevent backflow caused by both backsiphonage
and backpressure.* The RDCV prevents backflow caused by both backsiphonage
and backpressure, but is non-testable.
* The air gap can be
considered "testable" in the sense that it can be visually
inspected.
Residential Dual Check Valve:
The RDCV is a practical,
non-testable device that can be installed for containment protection at
residential homes. The RDCV is installed in-line and downstream of the
service meter, and contains no shutoff valves. The RDCV prevents backflow
caused by both backsiphonage and backpressure, but is recommended only for
residential homes which are considered to be a non-health hazard (see Figure
4.).
Figure 4. Residential Dual Check
Valve

Note: Check valves are in the
backflow position.
Atmospheric Vacuum Breaker:
The AVB is a non-testable
device that is installed at fixture outlets. The AVB prevents backflow
caused by backsiphonage, but not backpressure. The AVB must not be kept
under continuous pressure for more than 12 hours in any 24-hour period.
Because of this requirement, no shut-off valve should ever be installed
downstream of the AVB. A shutoff valve upstream of the AVB is recommended.
The AVB should be installed at least six inches above the fixture outlet
(see Figure 5.).
Figure 5. Atmospheric Vacuum
Breaker

Hose-Bibb Vacuum Breaker:
The HBVB is a non-testable
device that is installed at fixture outlets. The HBVB prevents backflow
caused by backsiphonage, but not backpressure (see Figure 6.).
Figure 6. Hose-Bibb Vacuum Breaker

Pressure Vacuum Breaker:
The PVB is a testable device
that is equipped with test cocks and shutoff valves, and is installed at
fixture outlets. The PVB prevents backflow caused by backsiphonage, but not
backpressure (see Figure 7.).
Figure 7. Pressure Vacuum Breaker

Table 1.
Recommended Backflow Prevention
Devices
The following table outlines the
applicability of the air gap, RPZD, and DCVA for the protection of a community
water supply. This is a partial list and is not intended to supplant any
ordinances or standards developed by a water company.
| |
TYPE OF DEVICE
TO BE USED
|
| PLANT
OR
FACILITY |
Air Gap |
RPZD |
DCVA |
| 1. Aircraft and
Missile Plants |
X |
X |
|
| 2. Automatic Car Wash |
X |
X |
|
| 3. Automated Manufacturing Plants |
X |
X |
|
| 4. Auxiliary Water Systems |
X |
X |
|
| 5. Beverage Bottling Plants |
|
|
X |
| 6.
Breweries/Distillers |
X |
X |
|
| 7. Chemical Plants
( Manufacturing, Processing, Compounding, or
Treatment) |
X |
X |
|
| 8. Dairies and Cold Storage Plants |
X |
X |
|
| 9. Dye Works |
X |
X |
|
| 10. Film Processing |
X |
X |
|
| 11. Irrigation Systems
(Green House, Park, Golf Course, Playgrounds, Estates, Cemeteries, etc.) |
X |
X |
|
| 12. Laboratories |
X |
X |
|
| 13. Laundries |
X |
X |
|
| 14. Meat Packing and Rendering Plants |
X |
X |
|
| 15. Metal Plating Plants |
X |
X |
|
|
16. Paper and Paper Products (Wet Process)
|
X |
X |
|
| 17. Petroleum or Gas Processing or Storage Plants |
X |
X |
|
| 18. Plating Plants |
X |
X |
|
19. Power Plants (Heating, Ventilation,
Refrigeration, or Commercial Power)
|
X |
X |
|
|
20. Rubber Plants (Natural or Synthetic, Mfg. Rubber Goods or
Tires)
|
X |
X |
|
| 21. Sand and Gravel Plant |
X |
X |
|
|
22. Sewage or Stormwater Treatment/Processing Facility; Ejector or Pumping Station
|
X |
X |
|
| 23. Swimming Pools |
|
|
X |
| 24. Water Front Facilities and Industries |
X |
X |
|
| 25. Where a Cross-Connection is to be Maintained |
X |
X |
|
| 26. Radioactive Materials or Substances,
Processing Plants or Facilities Handling |
X |
|
|
| 27. Manufacturing, Processing, and Fabrication
Plants Using Toxic Materials |
X |
X |
|
| 28. Manufacturing, Processing, and Fabrication
Plants Using Nontoxic Materials |
|
|
X |
| BUILDINGS |
|
|
|
| 29. Convalescent Home |
|
|
X |
| 30. Medical Clinic |
X |
X |
|
| 31. Medical/Dental Building |
X |
X |
|
| 32. Multipurpose Commercial Buildings
(Over three stories) |
|
|
X |
| 33. Office Building (Over three stories) |
|
|
X |
| 34. Hospitals |
X |
X |
|
| 35. Home for the Aged |
|
|
X |
| 36. Mortuary |
X |
X |
|
| 37. Morgue |
X |
X |
|
| 38. Nursing Home |
|
|
X |
| 39. Elementary, High Schools, Trade Schools, and
Colleges |
|
|
X |
| 40. Schools with Laboratories |
X |
X |
|
| 41. Apartment and/or Hotel with Restaurant |
|
|
X |
| 42. Apartment and/or Hotel (Over three stories) |
|
|
X |
| 43. Apartment and/or Hotel with House Pump
and/or Water Storage Tank |
X |
X |
|
| 44. Apartment and/or Hotel with House Pump
and/or Water Storage Tank |
|
|
X |
|
45. Public Building (Federal/State/City)
|
|
|
|
a. Potential Health Threat
|
X |
X |
|
b. Potential Pollution
|
|
|
X |
c. Restricted/Classified or Closed Facilities
|
X |
X |
|
| 46. Restaurant (Any Food Handling Establishment) |
|
|
X |
| 47. Supermarket |
|
|
X |
| 48. *Building with House Pump and/or Water
Storage Tank |
|
|
X |
| 49. *Building with Sewage Ejectors |
X |
X |
|
*Apply to any building regardless of building
purpose
FIRE PROTECTION SYSTEMS
A. No Protection
(No Device Required)
1.
Wet system, no pumper connection on
buildings three stories or less.
2.
Dry system, no pumper connection.
B. Double Check Valve Assembly
1.
Any system (wet or dry) with a pumper
connection.
2.
Wet system only within line booster pump
on building over three stories high.
3.
Any system with private hydrants.
C. Reduced Pressure Zone Device
1.
Any system where anti-freeze or inhibitors
are used.
2. Any system where an auxiliary water source
is available and connected to the fire
system.
Plumbing Codes
The following is a list of
plumbing codes which DEP is aware of at the time of the development of this part
of the Public Water Supply Manual. The purpose of this list is to provide
information on the availability of various plumbing codes and not to recommend a
preference for one code over another. Revisions of this list will be made in the
future, as information on other plumbing codes becomes available.
1. The BOCA Plumbing Code
The Building Officials and Code Administrators
International, Inc.
4051 West Flossmoor Road
Country Club Hills, Illinois, 60478
Telephone (708) 799-2300
2. The International Plumbing Code
The Building Officials and Code Administrators
International, Inc.
4051 West Flossmoor Road
Country Club Hills, Illinois, 60478
Telephone (312) 799-2300
3. The Uniform
Plumbing Code
The International Association of Plumbing and
Mechanical Officials
20001 Walnut Dr. South
Walnut, CA 91789
Telephone (909) 595-8449
Monroeville Municipal Authority
- Cross Connection Control Program
|